- Contact Person : Ms. Si Lisa
- Company Name : Henan Defy Electronics Co., Ltd.
- Tel : 0086-371-55819257
- Fax : 0086-371-66770722
- Address : Henan,Zhengzhou,7/F, Building 68, Enterprise Headquarters Base, High-Tech Development Zone
- Country/Region : China
DF-300 Handheld Three-Phase Meter
DF-300 Handheld Three-phase Can test the three-phase AC voltage, current, phase between voltage, phase between current, phase between voltage¤t, frequency, phase, active power, reactive power, apparent power, power factor, vector sum when the measurement circuit is not opened. It can also identify the transformer wiring group, inductive circuit, capacitive circuit, test the secondary circuit and bus bar protection system, read the phase relations of each CT of the differential protection system, check if the ammeter is wiring correctly, check the circuit and equipment. This device applies to electric power, petrochemical corporation, metallurgy, railway, industrial and mining enterprises, research institutions, metrology department, etc, especially applies to power quantity measurement system and relay protection system.
I. Features & Functions
1. Equipped with shock-proof, skid-proof, high insulating protective jacket.2. Uses 240×160 LCD, dynamic display, vector diagram indicates, easy to read.3. There are two models current clamp, the cuspate & small ones apply to positions of wire-intensive, the round & big ones apply to test the heavy gage wires.4. High precision, high stability, low power consumption.5. Safe, accurate, convenient.
II . Specifications
Influence factor | Reference conditions | Working conditions | Remark |
Temperature | 23°C±1°C | -10°C~40°C | / |
Humidity | 40%~60% | <80% | / |
Signal waveform | Sine wave | Sine wave | β=0.01 |
Signal frequency | 50HZ±1HZ | 45HZ~65HZ | / |
Working voltage | 9V±0.1V | 9V±1.5V | / |
Current amplitude when testing the phase frequency | 200mA±10mA | 2mA~20A | / |
Voltage amplitude when testing the phase frequency | 100V±20V | 10V~600V | / |
Current amplitude when testing the power factor | 200mA±10mA | 20mA~20A | / |
Voltage amplitude when testing the power factor | 100V±20V | 10V~600V | / |
External electric field, external magnetic field | Should avoid | ||
The position of the measured wire | Put the wire should be put at the geometric center of the jaw. |
category | Measurement range | Resolution | Intrinsic error |
voltage | AC 0.00V~600V | 0.01V | ±(1.5%rdg+3dgt) |
current | AC 0.0mA~20.0A | 0.1mA | ±(1.5%rdg+3dgt) |
phase | 0.0°~360° | 0.1° | ±1° |
Active power | 0.0W~12kW | 0.1W | ±(3%rdg+3dgt) |
Reactive power | 0.0VAR~12kVAR | 0.1VAR | ±(3%rdg+3dgt) |
Apparent power | 0.0VA~12kVA | 0.1VA | ±(3%rdg+3dgt) |
Frequency | 45HZ~65HZ | 0.01HZ | ±(2%rdg+3dgt) |
Power factor | -1~+1 | 0.001 | ±0.03 |
Note: phase error ±3° under working (phase error ±5° if current amplitude under 10mA).
( function(){ var aBigImageSrc = [ 'http://i00.i.aliimg.com/photo/v0/688389368_1/DF_300_Handheld_Three_Phase_Meter.jpg' , 'http://i00.i.aliimg.com/photo/v0/688389368_2/DF_300_Handheld_Three_Phase_Meter.jpg' , 'http://i00.i.aliimg.com/photo/v0/688389368_3/DF_300_Handheld_Three_Phase_Meter.jpg' , 'http://i00.i.aliimg.com/photo/v0/688389368_4/DF_300_Handheld_Three_Phase_Meter.jpg' ]; var oProductShow = new AE.run.minisite.productShow(); oProductShow.init( { 'aImgSrc': aBigImageSrc } ); } )(); DF-300 Handheld Three-Phase Meter